MNS Intelligent Low-Voltage Power Distribution System
By integrating intelligent sensing, communication, and data analytics technologies, it creates a digital power distribution hub that combines power distribution, monitoring, and energy management, helping users achieve intelligent operation & maintenance and optimized energy consumption.
KLMNS
The MNS Low-Voltage Switchgear is a fully type-tested (TTA) product that complies with international and national standards IEC 61439 and GB/T 7251. Designed around the core principles of safety, intelligence, flexibility, and durability, it features a modular structure and lean manufacturing processes. The system meets comprehensive power distribution needs across a wide range of applications, from industrial production to commercial buildings, and from traditional distribution to intelligent energy management.
The product offers high safety protection, digital monitoring, compact layout, and long service life, providing users with a stable, reliable, and energy-efficient low-voltage power distribution solution.
Advantages & Features
End-to-End Intelligent Integration: Compatible with intelligent circuit breakers, multifunction meters, temperature and humidity sensors, and other components, supporting full “remote measurement, remote signaling, and remote control” functions for real-time power distribution monitoring.
Accurate Monitoring and Early Warning: Real-time temperature monitoring of key busbars and contacts, with automatic over-temperature alerts to prevent overheating hazards; also features fault waveform recording, harmonic analysis, and power quality assessment to proactively identify potential issues.
Energy Efficiency Optimization: Precisely measures energy consumption for each circuit, generates visualized reports, quickly identifies energy-saving opportunities, and supports peak-valley electricity optimization to facilitate green, low-carbon operations.
Seamless Multi-System Integration: Supports mainstream industrial communication protocols such as Modbus, PROFINET, and EtherNet/IP, enabling seamless integration with DCS/EMS systems for coordinated global energy management.
Dual Protection with Arc Fault and Electrical Fire Monitoring: Provides proactive alerts to potential safety risks.
Remote Diagnosis and Maintenance Guidance: Reduces the need for on-site personnel and lowers operation & maintenance costs.
Multi-Platform Monitoring: Supports both mobile and PC terminals, enabling real-time access to power distribution status anytime, anywhere.
Historical Data Storage and Trend Analysis: Provides data support for equipment upgrades and energy consumption optimization.
Basic Technical Parameters
Rated Operating Voltage | V | 400V/450/500/550/660V AC |
Rated Insulation Voltage | V | 660V |
Rated Impulse Withstand Voltage | kV | 6/8/12 |
Overvoltage Category | Ⅳ | |
Rated Frequency | Hz | 50 |
Rated Current of Main Busbar | A | up to 6300 |
Rated Peak Withstand Current of Main Busbar | kA | up to 220 |
Rated Short-Time Withstand Current of Main Busbar | kA | up to 100 |
EMC Test | Class A |