GGD-Type AC Low-Voltage Switchgear Cabinet

The GGD-Type AC Low-Voltage Switchgear Cabinet is a fixed low-voltage distribution device designed with the principles of safety, economy, rationality, and reliability. It complies with GB/T 7251.12-2013 and IEC 60439-1 standards and is widely used in indoor low-voltage distribution systems of power plants, substations, industrial and mining enterprises, and commercial buildings. It performs the core functions of power conversion, distribution, and control for motors, lighting, and other distribution equipment.


Product Details

GGD-Type AC Low-Voltage Switchgear Cabinet

The GGD-Type AC Low-Voltage Switchgear Cabinet is a fixed low-voltage distribution device designed with the principles of safety, economy, rationality, and reliability. It complies with GB/T 7251.12-2013 and IEC 60439-1 standards and is widely used in indoor low-voltage distribution systems of power plants, substations, industrial and mining enterprises, and commercial buildings. It performs the core functions of power conversion, distribution, and control for motors, lighting, and other distribution equipment.

  • Tiered Protection Design: Protection ratings range from IP20 to IP40, with a default of IP30 for dust and touch protection. Upgradable to IP40 to suit humid and dusty environments. Cabinet doors feature rubber gaskets to block foreign object intrusion.

  • Strong Fault Withstand Capability: Short-circuit withstand current up to 31.5 kA, with excellent dynamic and thermal stability, allowing rapid interruption of fault currents to prevent accident escalation.

  • Full-Circuit Safety Isolation: The cabinet is divided into separate compartments for the main busbar, circuit breakers, and cables, ensuring organized wiring and minimizing circuit interference. Built-in grounding protection circuits and knurled grounding screws ensure reliable grounding.

  • Flame-Retardant Insulation Protection: Busbar clamps made of high flame-retardant PPO material provide high insulation strength and stable mechanical performance, preventing safety risks caused by insulation aging.

Basic Technical Parameters


Model

Rated Working Voltage (V)

Rated Insulation Voltage (V)

Control Voltage (V)

Rated Current (A)

Rated Short-Circuit Breaking Capacity (kA)

Rated Short-Time Withstand Current (1s, kA)

Rated Peak Withstand Current (kA)

GGD1

380

660

220 / 380

A

1000

15

15

30

B

600 (630)

C

400

GGD2

380

660

220 / 380

A

1500 (1600)

30

30

63

B

1000

C

630

GGD3

380

660

220 / 380

A

3150

50

50

105

B

2500

C

2000

GGD

380 / 400 / 450 / 500 / 660

660

220 / 380

A

6300

100

100

220

B

5000

C

4000